close Warning: Can't synchronize with repository "(default)" (Unsupported version control system "svn": Can't find an appropriate component, maybe the corresponding plugin was not enabled? ). Look in the Trac log for more information.

Changes between Initial Version and Version 1 of ControlLogicFeatures


Ignore:
Timestamp:
Dec 14, 2007 11:46:08 AM (17 years ago)
Author:
anonymous
Comment:

--

Legend:

Unmodified
Added
Removed
Modified
  • ControlLogicFeatures

    v1 v1  
     1{{{
     2#!rst
     3
     4Control Logic Operation and Features of ianBMS
     5===============================================
     6
     7Lighting control
     8----------------
     9
     10Lights are controlled using bistable (ratchet) relays. A bistable relay is energized to change state
     11from open to closed and vice versa. Once its state changes the relay remains in the new state until
     12it receives the next energization stimulus. One bistable is used for every lighting load (one or
     13more fixtures). The bistables are controlled by the RSC.
     14
     15Push-buttons are installed to allow the occupants manually toggle the lighting loads (typically
     16one button per load, but more in some spaces like hallways). The push-buttons are connected to controller
     17digital inputs therefore their association to lighting loads can be modified by reconfiguring the controller
     18logic. The occupants can also control the lights though a simple web-based HMI, as well as see the current
     19condition of all the lights in the building.
     20 
     21Apart from manual lights control, the system also provides auto switch-off functionality during
     22after-hours. Auto switch-off will be activated when all three conditions are met:
     23
     24- It is after 20:00 in the evening and before 08:00 in the morning, or it is a non-working day
     25- The illuminated space is not occupied, and has remained unoccupied for at least 15 minutes
     26- The pushbuttons controlling the load have not been pressed for at least 15 minutes
     27- No HMI command has been issued to turn-on the loads for at least 15 minutes
     28
     29If no motion sensor is installed in a room, or if a motion sensor is removed or stops to function
     30the system considers the room "always occupied" and acts accordingly.
     31
     32For some rooms (e.g. rarely visited storage rooms), auto switch-off functionality is enabled during
     33working hours as well. For these rooms, if no motion sensor is present to determine occupancy the lights
     34are switched-off after 15 minutes regardless of occupant presence.
     35
     36For the restrooms the auto switch-off functionality is also enabled during working hours. The switch-off
     37delay is set to 30minutes (instead of 15).
     38
     39A global "leave the building" push-button is also provided which, when pressed, switches off
     40all the lights with the exception of the ones illuminating the exit hallway; these are turned on and
     41remain on for 2 minutes permitting the occupant to leave the building.
     42
     43If controller fails to change the state of a load (fails turn off or on a light), then after
     4410 retries it declares the bistable relay malfunctioning and raises the respective failure alarm.
     45
     46
     47Air conditioning
     48----------------
     49
     50Ceiling mounted fan-coil units are used for air-conditioning the office space. They can operate in three
     51fan speeds (low, medium, high). The temperature in each room will be measured by the controller (using temperature sensors)
     52and the fan-coils will be switched on and off as well as between speeds in order to achieve a
     53set-point. Through the web HMI the occupant will be able to control:
     54
     55- The speed of the fans. Four options will be given: off, low, med, high, auto.
     56- The set-point temperature. The occupant will be able to configure the setpoint temperature between
     57  18 and 28 degrees celcius
     58
     59Regardless of the set-point and fan-speed configured by the occupant, the system will fall-back to
     60a special "unocupied" operating mode when all the following conditions are met:
     61
     62- It is after 20:00 in the evening and before 08:00 in the morning, or it is a non-working day
     63- The room is not occupied, and has remained unoccupied for at least 10 minutes
     64
     65In unoccupied mode a predefined (non occupant-configurable) set-point will be used.
     66With this setpoint---which will be rather low durring heating season, and rather high during
     67cooling season---energy will be conserved when the building is unmanned. Through the web-HMI the occupant
     68will be able to set the room back to normal air-conditioning mode even durring after hours. Once the room
     69is manually set to normal mode, it will remain so for at least 1 hour, then it will switch-back to
     70unoccupied mode provided that the conditions above are still satisfied (i.e. that it is still before 08:00,
     71and the room is still unoccupied).
     72
     73At 08:00 in the morning the system will enter "boost" mode, whereby the fan-coil unit will operate at full
     74capacity until the occupant-configurable setpoint is reached. Boost-mode helps bring the office-space back
     75to normal temperature quickly.
     76
     77To better understand the operation of the system consider the following example scenario:
     78
     79The user has set the fan-speed to "auto", and the setpoint to 22 degC. The administrator has set the
     80unoccupied-mode setpoint to 16 degC. The occupant leaves the room at 19:00, at which point the temperature has
     81been stabilized at the setpoint (22 degC). The room will be kept at this temperature until 20:00 at which
     82time---given that the room is unoccupied and has remained so for more than 10 minutes---the system will
     83set the room to "unoccupied" mode. The fan-coil will be switched-off for the night and will be turned on
     84only if the temperature drops below 16 degC. At 23:00 the occupant enters the room, and using the web
     85HMI sets the air conditioning system back to normal mode.
     86The fan-coil starts operating in order to bring the room temperature back
     87to the setpoint (to 22 degC). The room will remain at "normal" mode for at least 1-hour, even if
     88the occupant departs earlier. While this not the most efficient setting, it limits the reliance on the
     89occupancy sensor and reduces the amount of inconvinience in case of a sensor failure: That is, if the sensor
     90is not working, and the occupant wishes to remain in the building after-hours he has to re-set the
     91system to "normal" mode once every hour. Of course if the sensor is working properly the system will remain
     92in "normal" mode, as long as the occupant is present.
     93
     94In order to protect the electrical installation from transient over loading, air-conditioning loads
     95will be actuated using "delayed loading" logic than will guarantee a minimum spacing
     96of 5 seconds between to consecutive load activations. This will be especially useful when boost mode is
     97activated in the morning 
     98
     99
     100Server room free cooling
     101------------------------
     102
     103The server room will be cooled by two systems: A split-unit air conditioner, and a free-cooling air exchange
     104system. The air-conditioner will operate autonomously using a constant set-point. The free-cooling system
     105will operate under the control of the RSC. The controller will measure the internal and external temperature
     106and humidity and calculate the respective enthalpy values. If the external enthalpy is lower than the internal enthalpy and the external humidity is lower than a given level, air from outside will be fed to the room by
     107activating the fan of the free-cooling system. Using free cooling the room temperature will be allowed to drop
     108considerably below the air-conditioning set-point, respecting only a failsafe limit. Bringing the server
     109room temperature below the setpoint, will force the air-conditioning system to turn its compressor off,
     110thus conserving energy. The energy consumption of (the current drawn by) both the split unit air-conditioner,
     111as well as the free cooling system will be measured by the controller and logged in order to permit an
     112estimation of the efficiency of the system. The temperature and humidity inside the server room will also
     113be monitored, and logged every 5 minutes. Logs---for temperature and energy consumption---will be held in
     114the controller's memory for one week. Alarms will be generated for high temperature and high humidity inside
     115the server room
     116
     117Occupancy monitoring
     118--------------------
     119
     120Consumption measurement
     121-----------------------
     122
     123Other alarms
     124------------
     125
     126Web HMI main screen
     127-------------------
     128
     129- Current room temperature (read only)
     130- Normal mode temperature-setpoint (configurable)
     131- Unoccupied mode temperature setpoint (read only)
     132- Air conditioning unit fan-speed setting (configurable)
     133- Air conditioning unit actual fan-speed (read only)
     134- Lights status, and "activate" / "deactivate" commands
     135- Current occupancy indication
     136- External temperature
     137- External humidity
     138
     139- Smoke detection alarm for server room, kitchen, hardware room, and hallways
     140  (3 indications)
     141- Leak detection alarm for restrooms and kitchen
     142
     143}}}